61
Section 21: Listing Requirements
21.1 UL Listed Commercial Burglary and Resi-
dential Burglary/Fire Installations
The installation requirements listed below must be met for
the following grades of service.
Grade AA Central Station and Police Connect
The installation must use T-Link module which communi-
cates over LAN/WAN to the Sur-Gard MLR-IP receiver.
Polling time must be 90 seconds. Compromise detection
time must be 6 minutes.
Grade A Local
The installation must have a bell UL Listed for mercantile
local alarms (AMSECO MBL10B).
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure
(UL Listed DSC models CMC-1, PC4004C, PC4050CAR/or
PC4050CRAR).
Grade B Central Station and Grade A Police Connect
The installation must have a bell UL Listed for mercantile
local alarms (AMSECO MBL10B).
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure
(UL Listed DSC models CMC-1, PC4004C, PC4050CAR/or
PC4050CRAR).
Grade C Central Station
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure
(UL Listed DSC models CMC-1, PC4004C, PC4050CAR/or
PC4050CRAR).
All Commercial Installations
The entry delay must not exceed 60 seconds
The exit delay must not exceed 60 seconds.
The minimum bell cutoff time is 15 minutes.
Residential Installations
The entry delay must not exceed 45 seconds
The exit delay must not exceed 60 seconds.
The minimum bell cut-off time is 4 minutes.
Programming
The notes in the programming sections describing the sys-
tem configurations for UL Listed installations must be
implemented.
Control of the Protected Premises
In order to have a UL Certificated system the protected area
is to be under the responsibility of one ownership and man-
agement (i.e. one business under one name). This may be a
group of buildings attached or unattached with different
addresses but under the responsibility of someone having
mutual interest. The person of mutual interest is not the
alarm installing company.
Bell Location
The alarm sounding device (bell) must be located where it
can be heard by the person or persons responsible for main-
taining the security system during the daily arming cycle.
Protection of the Control Unit
The local control and the local power supply must be pro-
tected by one of the following ways:
The control unit and audible alarm device must be in a
protected area which is armed 24 hours a day.
Each partition shall arm the area protecting the control
unit and the audible alarm device power supply. This
may require duplicate protection armed by each parti-
tion. Access to this protected area, without causing an
alarm, will require that all partitions be disarmed.
In all cases described above, the protected area for the con-
trol unit must be programmed as not bypassable.
Casual Users
The installer should caution the user(s) to not give system
information to casual users (e.g. codes, bypass methods,
etc. to baby-sitters or service people). Only the One-Time
Use codes should be given to casual users.
User Information
The installer should advise the users and note in the user
instruction manual:
Service organization name and telephone number
The programmed exit time
The programmed entry time
21.2 Commercial Fire Alarm Installations
System Specifications
Class B / Style B 2-Wire Smoke Detector Supervision
Class B/ Style B Waterflow Supervision
Notification Appliance Circuit Supervision
Service Type: Automatic, Manual, Sprinkler Supervi-
sory, Waterflow
Signaling Type: Non-coded
Ground Fault Supervision
Supervised Dual Telephone Lines
PC4XXX modules other than those specified have not been
investigated by UL for use with commercial fire alarm sys-
tems and cannot be used for commercial fire service.
All other modules providing burglary sevice must be pro-
vided in a separate enclosure.
2-Wire Smoke Detector Compatibility
Maximum loop resistance: 100 ohms
Operating Voltage Range: 8.9 - 12.0
Maximum Alarm Current: 80 mA
Compatibility Identifier: FM-2
The following 2-wire smoke detectors are compatible
with the PC4020CF/PC4701:
Manufacturer Model Base Type
DSC MN-220 None Photo
DSC MN-220T None Photo w/ heat
System Sensor 1100 None Ion
System Sensor 2100D None Photo
System Sensor 2100T None Photo w/ heat
System Sensor 2400 None Photo
System Sensor 1400 None Ion
System Sensor 1151 B401 Ion
System Sensor 2151 B401 Photo
System Sensor
1151 B110LP Ion
System Sensor
2151 B110LP Photo
System Sensor
1451 B401 Ion
System Sensor
1451 B401B Ion
DSC
FSA-210B None Photo