55
Other types of zones may also be assigned to this parti-
tion without effecting the fire operation as described
below.
Operation
On alarm, from any fire zone in this partition, the fire auto-
scroll display will only show on keypads assigned to the
fire partition and on any system global keypads.
The waterflow and 2-wire smoke zones on the PC4701
module will show, in the auto-scroll mode, on all
partition
and global keypads. If a zone on the PC4701 is in alarm,
then fire silence and reset can be done from any partition
keypad.
If the alarm is from a partition zone (not PC4701) then fire
alarm silence and reset can only be done directly on the fire
partition keypad(s). To silence from other partition keypads
or a global keypad requires that the keypad be loaned to the
fire partition.
Fire Configuration 2 (Recommended)
Assign ALL fire zones to ALL active partitions in the
system. Do not program fire zones as ‘silent’.
PC4702 Bell zones automatically respond to any fire
zone in the system and can be assigned to any partition.
Zones on the PC4701 module are always global and do
not require partition assignment.
One or more fire keypads may be located on any parti-
tion.
Operation
On alarm, the fire auto-scroll display will show on all parti-
tion keypads and on all global keypads.
Fire alarm silence and fire system reset may be done
directly on any
partition keypad. To silence from a global
keypad requires that the global keypad be loaned to one of
the partitions.
NOTE: Assign command output 2 (sensor reset) to all parti-
tions.