PowerSeries Neo Installation Guide
Specifications
Zone Configuration
l 16, 32, 64, or 128 wireless zones supported and up to 8 hardwired zones avail-
able on the controller
l 40 zone types and 14 programmable zone attributes
l Zone configurations available: normally closed, single EOL and DEOL
supervised
l Hardwired zone expansion (fully supervised) available using the model
HSM2108 (eight zone expander module)
l Wireless zone expansion (fully supervised) available using the HSM2Host 2-
way wireless integration module operating at 915MHz (North America),
433MHz (Europe) and 868MHz (international)
Access Codes
l Up to 1002 access codes: 1000 (level 2-EN), one installer code (level 3-
EN), and one maintenance code
l Programmable attributes for each user code
l When using 8-digit access codes, the minimum number of variations are:
HS2016-4: 2083333
HS2032: 1388888
HS2064/HS2128: 1052631
HS2064 E: 200000
HS2128 E: 100000
Warning Device Output
l Integral sounder capable of 85 dB @ 3m, self-powered type Z
l 2 remote, wireless indoor/outdoor warning devices supported: models
PGX901 (indoor), PGX911 (outdoor) (X=4, 8, or 9)
l Programmable as steady, pulsed or temporal three (as per ISO8201) and tem-
poral four (CO alarm) output
l Warning device sounds alarms in the following priority: fire, CO, burg
Note: For NFA2P certified systems the delay for operating the warning device
shall be set to max. 10 min.
Memory
l CMOS EEPROM memory
l Retains programming and system status on AC or battery failure for 20 years
min. (not verified by UL)
Transformer: DSC PTD1640U, PTC1640U,PTC1640UG, PTC1640CG
Primary: 120V, 60Hz Class II
Secondary: 16.5VAC, 40VA Max.
Regulated power supply:
l 700mA auxiliary supply, 12V DC
l Positive temperature coefficient (PTC) for Bell, Aux+ and Battery terminals
l Reverse battery detection/protection
l Supervision for AC power and low battery
l Normal and high current battery charge options
l Supervised battery charging circuit
Current draw (panel):
l 85mA (nominal) 2A(Max)
Bell Output:
l 12V, 700mA supervised (1k Ohm) bell output (current limited at 2 amps)
l Steady, Pulsed, Temporal 3 fire, Temporal 4 CO alarm cadences
l Bell short detection (software + hardware)
Aux+:
l Voltage range = 9.6V - 13.8V DC
l Current = 700mA (shared with Corbus R(ed))
l Output ripple voltage: 270mVp-p max.
l Onboard programmable outputs:
l PGM 1 - 50mA switched programmable output
l PGM 2 - 300mA current-limited switched programmable output. 2-Wire
smoke detectors (90mA current limited) are supported using this PGM
l PGM 3 - 50mA switched programmable output
l PGM 4 - 50mA switched programmable output
l Hardware PGM over current protection
Battery
l 12V sealed lead acid, rechargeable
l Battery capacity:
l 4 hours (UL commercial burglary/residential burglary),
l 12 hours (EN50131),
l 24 hours INCERT [Belgium]
Note: For T 014 compliance (INCERT certification), only 14Ah (2x7Ah)
batteries were tested and are accepted for INCERT certified systems.
l Maximum standby time: 24 hours (with 14Ah battery and Aux current limited
to 470mA)
l Recharging time to 80% 72 hours
l Recharging rate: 240mA (12 hours max.), 480mA (24 hour backup)
l Backup time: 24 hours (UL)
l Battery lifespan: 3-5 years
l Low battery trouble indication threshold 11.5VDC
l Battery restore voltage 12.5V
l Main board current draw (battery only):
l HS2016/32/64/128 (no alternate communicator) standby 85mA DC
l HS2016/32/64/128, (including alternate communicator) standby 190mA
DC
l Transmit (alternate communicator module) 195mA DC
l Resettable fuses (PTC) used on circuit board
l Supervision for loss of primary power source (AC fail), battery loss or bat-
tery low voltage (battery trouble) with indication provided on the keypad
l Internal clock locked to AC power frequency
Operating Environmental Conditions
l Temperature range: UL= 0°C to +49°C (32°F-120°F),
l Relative humidity: <93% non condensing
Alarm Transmitter Equipment (ATE) Specification
l Digital dialer integral to the main control board
l Supports SIA and Contact ID
l Complies with TS203 021-1, -2, -3 Telecom equipment requirements and
EN50136-1-1, EN50136-2-1, EN50136-2-3 ATS 2
l Optional Dual IP/Cellular communicators (3G2080(R)E/ TL2803G(R)E/
TL280(R)E) can be installed in the same enclosure and configured as
primary or back-up, with AES 128-bit encryption
l Compliant with EN50136-1-1, EN50136-2-1 ATS2 requirements
System Supervision Features
The PowerSeries Neo continuously monitors a number of possible trouble
conditions and provides audible and visual indication at the keypad. Trouble
conditions include:
l AC power failure
l Zone trouble
l Fire trouble
l Telephone line trouble
l Communicator trouble
l Low battery condition
l RF jam
l AUX power supply fault
l Failure to communicate
l Module fault (supervisory or tamper)
Additional Features
l 2-way wireless device support
l Visual verification (images + audio)*
l Proximity tag support
l PGM scheduling
l Quick arming
l User, partition, module, zone and system labels
l Soak test*
l Programmable system loop response
l Keypad and panel software versions viewable through keypad
l Doorbell zone type
l Low battery PGM type
*Feature not evaluated by UL/ULC.
- 9 -