6.5.8Randomgenerator
Shortdescription
Theoutputofarandomgeneratoristoggledwithinaconfigurabletime.
Connection Description
Input En Thepositiveedge(0to1transition)attheenableinputEn
(Enable)triggerstheondelayfortherandomgenerator.
Thenegativeedge(1to0transition)triggerstheoff
delay
fortherandomgenerator.
Parameter TH: Theondelayisdeterminedatrandomandlies
between0sandT
H
.
TL: Theoffdelayisdeterminedatrandomandlies
between0sandT
L
.
Output Q QissetonexpirationoftheondelayifEnisstillset.Itis
resetwhentheoffdelaytimehasexpiredandifEnhasnot
beensetagain.
Parameter
Theon-delaytimeTHandtheoff-delaytimeTLcanbeprovidedbytheactualvalueofanother
already-programmedfunction:
Analogcomparator:Ax Ay
Analogtrigger:Ax
Analogamplifier:Ax
Analogmultiplexer:AQ
Analogramp:AQ
Analogmath:AQ
PIcontroller:AQ
Datalatchingrelay:AQ
Up/Downcounter:Cnt
Thevalueof "T","L"canbeset/modifiedinparametermode.Forinformationabouthowto
modify,refertochapter5.2.2please.