EasyManua.ls Logo

Easy Electronics xLogic Micro PLC - Hours Counter

Easy Electronics xLogic Micro PLC
293 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
134
theoutputis0andthepulsesatinputCntarenotcounted.
OutputQissetandresetaccordingtotheactualvalueatCntandthesetthresholds.Seethefollowing
rulesforcalculation.
Calculationrule
Iftheonthreshold>=offthreshold,then:
Q=1,ifCnt>=On
Q=0,ifCnt<Off.
Iftheonthreshold<offthreshold,then:
Q=1,ifOn<=Cnt<Off.
Caution
Thefunctionpollsthelimitvalueofthecounteronceineachcycle.
Thus,ifthepulsesatthefastinputs(ELC-12)orIB/IC(ELC-18)arefasterthanthescancycletime,the
SFBmightnotswitchuntilthesospecifiedlimithasbeenexceeded.
Example:Upto100pulsespercyclecanbecounted;900pulseshavebeencountedsofar.On=950;Off
=10000.Theoutputissetinthenextcycle,afterthevaluehasreached1000.
TheoutputwouldnotbesetatallifthevalueOff=980
6.5.14Hourscounter
Shortdescription
Aconfiguredtimeistriggeredwithasignalatthemonitoringinput.Theoutputissetwhenthistimehas
expired.
Connection Description
Input R Apositiveedge(0to1transition)atinputRresetsoutputQ
andsetsaconfiguredvalueMIatthecounterforthe
durationofthetime-to-go(MN).
Input En Enisthemonitoringinput.xLogicscanstheon-timeofthis
input.
Input Ral ApositiveedgeatinputRal(Resetall)resetsboththehours
counter(OT)andtheoutput,andsetstheconfiguredvalue
MIatthecountertoforthedurationofthetime-to-go(MN).
Thatis,
OutputQ=0,
ThemeasuredoperatinghoursOT=0,and
Thetime-to-goofthemaintenanceinterval
MN=MI.
Parameter MI:Maintenanceintervaltobespecifiedinhourunits

Table of Contents