EasyManua.ls Logo

Easy Electronics xLogic Micro PLC - Analog Differential Trigger

Easy Electronics xLogic Micro PLC
293 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
163
6.5.25Analogdifferentialtrigger
Shortdescription
Theoutputissetandresetdependingonaconfigurablethresholdandadifferentialvalue.
Connection Description
Input Ax Youapplytheanalogsignal
tobeanalyzedatinputAx.
Usetheanaloginputs
AI1...AI8,theanalogoutputs
AQ1andAQ2.
0-10Visproportionalto0-
1000(internalvalue).
Parameter A: Gain
Rangeofvalues: ± 10.00
B: Zerooffset
Rangeofvalues: ± 10,000
On:Onthreshold
Rangeofvalues: ±20,000
Delta: Differentialvaluefor
calculatingtheoffparameter
Rangeofvalues: ± 20,000
p: Numberofdecimals
Rangeofvalues:0,1,2,3
Output Q Qissetorreset,depending
onthethresholdand
differencevalues.
Parameterp(numberofdecimals)
AppliesonlytothedisplayofOn,OffandAxvaluesinamessagetext.
DoesnotapplytothecomparisonofOnandOffvalues!(Thecomparefunctionignoresthedecimal
point.)
TimingdiagramA:FunctionwithnegativedifferenceDelta

Table of Contents