160
Rangeofvalues: ± 10.00
B: Zerooffset
Rangeofvalues: ± 10000
p: Numberofdecimals
Rangeofvalues:0,1,2,3
OutputAQ
Analogoutput
ValuerangeforAQ:
-32768...+32767
Parameterp(numberofdecimals)
AppliesonlytothedisplayofAxandAyvaluesinamessagetext.
DoesnotapplytothecomparisonofOnandOffvalues!(Thecomparefunctionignoresthedecimal
point.)
Descriptionofthefunction
ThefunctionreadsthevalueofananalogsignalattheanaloginputAx.
ThisvalueismultipliedbythegainparameterA.ParameterB(offset)isaddedtotheproduct,i.e.
(Ax gain)+offset=ActualvalueAx.
SettingtheParparameter
Thegainandoffsetparametersareusedtoadaptthesensorstotherelevantapplication.
Viewinprogrammingmode(example):
Viewinparameterassignmentmode(example):
6.5.24Analogvaluemonitoring