A.2Technicaldata:xLogic(ELCseries)
Standard CPU
Units(ELC-6series)
ELC-6AC-R ELC-6DC-D-R ELC-6DC-D-TN
Inputs 4digital 4digital 4digital
ofwhichcanbeusedin
analogmode
none none none
Input/supplyvoltage 110-240VAC 12-24VDC 12-24VDC
Permissiblerange
withsignal 0
withsignal 1
Inputcurrent
85...265VAC
100...253VDC
max.40VAC0.03mA
min.79VAC,0.08mA
10.8V...28.8VDC
max.3VDC,1mA
min.8VDC,1.5mA
10.8V...28.8VDC
max.3VDC,1mA
min.8VDC,1.5mA
Outputs 2relays 2relays 2transistors(PNP)
Continuouscurrent 10Awithresistive
load;
2Awithinductiveload
10Awithresistiveload;
2Awithinductiveload
0.3A
Short-circuitprotection Externalfuserequired Externalfuserequired Externalfuserequired
Switchingfrequency 2Hzwithresistive
load;
0.5Hzwithinductive
load
2Hzwithresistiveload;
0.5Hzwithinductiveload
10Hz
Cycletime <0.1ms/function <0.1ms/function <0.1ms/function
Integratedtimeswitches/
powerreserve
Yes/typ.72h Yes/typ.72h Yes/typ.72h
Connectioncables
2x1.5mm² or1x2.5mm²
Ambienttemperature -20to+55 ºC
Storagetemperature 40 ºCto+70 ºC
Degreeofprotection IP20
Certification CE
Mounting On35mmstandardmountingrail,4MW,orwall-mounting
Dimensions WxHxD(48*90*64
mm)
Programmingcable PCcable,(RS232or
USB)
PCcable,(RS232orUSB) PCcable,(RS232or
USB)
xLogic<=>xLogic
communication(RS485)
No No No
xLogic<=>network
(Ethernet)
No No No
Thirdpartydevice(HMI) Yes(modbus) Yes(modbus) Yes(modbus)

Table of Contents