EasyIO FW Series – User Reference v3.0
8
Input Output configuration
FW Series range of products comes in few options.
Options are referring to IO (Input/Output) configurations.
Sedona
BACnet IP and MSTP Client
BACnet IP server
Modbus RTU Master
Sedona
BACnet IP and MSTP Client
BACnet IP server
Modbus RTU Master
Sedona
BACnet IP and MSTP Client
BACnet IP server
Modbus RTU Master
Sedona
BACnet IP and MSTP Client
BACnet IP server
Modbus RTU Master
RS485 Connection
RS485 connection must be terminated at both ends with termination resistor, typically 120 Ohms. It is
recommended to use shielded twisted pair wire (STP) for the wiring.
Lightning protection circuit is highly recommended to be installed at one end of the wiring. The controller
should be wired in daisy chain network topology as shown as image below. If wire branch can be avoided,
keep it as short as possible, and never connect more than one device to the wire branch (it is not
recommended).
Be careful if single power supply is used for all connected RS485 device, make sure all devices are
having the same ground connection. Make sure you are connecting the same wire for the same
terminal position, all “H” terminals connected to the same wire.
BUS A,B
Two Wire, Half Duplex
Speed: BACnet MSTP (9.6K, 19.2k, 38.4K)
Modbus RTU (9.6K, 19.2k, 38.4K, 57.6K, 115.2K),
IP, TCP, UDP, ICMP, HTTP,FTP
Application Support
(IP)
(Serial)
Sedona, BACnet IP Server , Tcom
BACnet MSTP Client OR Modbus RTU Master