SH-TSX Product Manual - © EasyIO / www.easyio.eu
Default 0 = DisabledNote:
Disabled removes the text and
measurement from the display.
1 = Room
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
140
Sensor 2 Text (RI2/Network)
Default: 0 = DisabledNote:
Disabled removes the text and
measurement from the display.
Unsigned 16
0..15
141
Sensor 3 Text (Built-in / Network
Sensor) Default: 1 = RoomNote:
Disabled removes the text and
measurement from the display.
Unsigned 16
0..15
142
Sensor 2 Source
Unsigned 16
0..1
0 = RI1
1 = Network Sensor
(Default)
143
Sensor 2 Network Temperature
Signed 16
-580…1220
-58.0…122.0°C/°F
(Default 0.0)
159
Disable ECO Button User Cancel
Signed 16
0..1
0 = Enabled (Default)
1 = Disabled
300
Modbus Address
Unsigned 16
0..247
0..247 (Default 1)
301
Modbus Baud Rate
Unsigned 16
0..4
0 = 9600 (Default)
1 = 19200
2 = 38400
3 = 57600
4 = 76800
302
Modbus Parity
Unsigned 16
0..2
0 = None (Default)
1 = Odd
2 = Even
303
Stop Bits
Unsigned 16
0..1
0 = 1 Stop Bit (Default)
1 = 2 Stop Bits
304
Screen Refresh Rate
Unsigned 16
0..2
0 = Fast (Default)
1 = Medium
2 = Slow
400
Force Reset
Unsigned 16
0..1
0 = Normal
1 = Force Reset
401
Non Volatile Memory Update
Unsigned 16
0..1
0 = Normal
1 = Update
403
Force Factory Defaults
Unsigned 16
0..1
0 = Normal
1 = Force Factory
Defaults
BACnet Interoperability Building Blocks Supported
(Annex K)
Application Service
Initiate
Execute
BIBB
ReadProperty
Yes
DS-RP-B
ReadPropertyMultiple
Yes
DS-RPM-B
WriteProperty
Yes
DS-WP-B
ReinitializeDevice
Yes
Who-Is
Yes
DM-DDB-B
I-Am
Yes