Eaton 93PM UPS 480V Three-Wire 100 kW Frame Installation and Operation Manual 164000227—Rev 07 97
77..22..88 SSyysstteemm CCoonnttrroollss
Tap the CONTROLS tab on the main menu navigation bar to display the Controls screen. Double conversion
operation, transfer to bypass, shutdown, and charger control commands are controlled through this screen. In
addition, the screen displays the current status of the UPS.
Table 23 describes the control functions and provides instructions to access and use the command menu
screens.
Table 24 lists the typical System Status Screen Messages that are displayed during UPS operation.
For UPS operating instructions using the System Controls, see paragraph 7.3 Single UPS Operation or
7.4 Multiple External Parallel System Operation.
Figure 62 through Figure 66 show the major control screens.
Table 23. Controls Menu Operation
Function Subfunction
Operation
System
Controls
The CONTROLS tab on the main menu navigation bar displays the
System Controls screen.
System Status GO ONLINE starts the UPS in Double Conversion mode or transfers the
UPS to Double Conversion mode from Bypass mode.
Bypass GO TO BYPASS starts the UPS in Bypass mode or transfers the UPS
to Bypass mode from Double Conversion mode.
Charger TURN ON CHARGER/TURN OFF CHARGER sets the battery charger
on or off.
Battery Test RUN BATTERY TEST starts the battery test.
Table 24. Typical System Status Messages
Function
Message
UPS Double Conversion; Bypass; ESS
Bypass Off; On; Available
Charger Charger Resting; Charger
UPS Operating Instructions