Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07 105
To start the battery test:
1. Tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed.
2. Tap the UPS CONTROLS tab on the secondary navigation bar. The UPS Control screen is displayed.
3. Tap the RUN BATTERY TEST button.
77..33..1155 UUssiinngg tthhee UUPPSS LLOOAADD OOFFFF CCoommmmaanndd
A UPS shutdown is initiated by the LOAD OFF command on the UPS Control screen. The UPS LOAD OFF
controls the UPS output by powering down the UPS and de-energizing the critical load.
The UPS (including Bypass) remains off until restarted.
To use the LOAD OFF command:
1. Tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed.
CAUTION
All power to the critical load is lost when LOAD OFF is selected in the following step. You should use this
feature only when you want to de-energize the critical load.
2. Tap the LOAD OFF button.
An action confirmation screen is displayed. Follow the on screen prompts to shut down the UPS or to
cancel the shutdown. Selecting YES will immediately shut down the UPS and de-energize the critical load.
Selecting NO will abort the shutdown.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.
3. To restart the UPS after using the LOAD OFF follow the procedure in paragraph
7.3.1 Starting the UPS in Double Conversion Mode or 7.3.2 Starting the UPS in Bypass Mode.
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers
are opened. Wait at least 5 minutes before accessing internal components.
77..33..1166 UUssiinngg tthhee RReemmoottee EEmmeerrggeennccyy PPoowweerr--ooffff SSwwiittcchh
WARNING
Emergency Power Off (EPO) and Remote Emergency Power Off (REPO) functionality is disabled for UPS
systems configured for UL 924 auxiliary lighting. To remove power from the system a LOAD OFF command
(see paragraph 7.3.15 Using the UPS LOAD OFF Command) must be given using the front panel controls and
all breakers opened.
A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this
switch to control the UPS output. The REPO switch de-energizes the critical load and powers down the UPS
immediately, without asking for verification.
The UPS, including Bypass, remains off until restarted.
UPS Operating Instructions