22 Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
Figure 8. UPS Cabinet Center of Gravity
Dimensions are in millimeters [Inches]
Weight and Center of Gravity (letters A, B, and C map to Figure 8)
A
mm (in)
B
mm (in)
C
mm (in)
Weight
kg (lb)
Eaton 93PM-100-1 UPS
842 (33.1) 537 (21.1) 276 (10.8) 337 (743)
Eaton 93PM-100-2 UPS
921 (36.3) 537 (21.1) 276 (10.8) 394 (869)
Eaton 93PM-100-3 UPS 1022 (40.2) 537 (21.1) 276 (10.8) 470 (1037)