26 Eaton 93PM UPS 480V Three-Wire 100 kW Frame Installation and Operation Manual 164000227—Rev 07
The tie cabinet must contain Module Output Breakers (MOBs) with dual auxiliary contacts for control of
the system. Without dual auxiliary MOBs, UPMs are not allowed to go to bypass individually during
servicing. All UPMs will go to bypass instead of the UPM needing service, decreasing critical load
protection.
External parallel system wiring length should be in accordance with Figure 11, to ensure approximately
equal current sharing when in bypass mode.
Figure 11. 93PM External Parallel Wire Length
NOTE Required parallel system wiring lengthmustbe equal to ensure approximately equal current sharingwhen in Bypassmode. For
proper operationthe following must be true:
1A =2A=3A =4A
1B =2B=3B =4B
NOTE Anydifferenceinwirelengthwill result in decreased capacityofthe UPS system while on bypass. Forexample,a10% difference
between thelongest and shortest wire lengths will result inadecreaseinbypasscapacityof 10%.
BypassInput to UPSUnits
UPS1
Battery
UPS2
UPS3
UPS4
Output fromUPS Units
Battery
Battery
Battery
1A
2A
3A
4A
1B
2B
3B
4B
For external wiring recommendations, including the minimum AWG size of external wiring, see Table 4 or
Table 5. Wire sizes listed are for copper wiring only.