36 Eaton 93PM UPS 480V Three-Wire 100 kW Frame Installation and Operation Manual 164000227—Rev 07
Use twisted-pair wires for each input and return or common.
All interface wiring and conduit is to be supplied by the customer.
When installing external interface wiring between a building alarm, relay output, battery breaker trip, or
Minislot and the UPS interface terminals, conduit must be installed between each device and the UPS
cabinet.
If using conduit, install the interface wiring in separate conduit from the power wiring.
All building alarm inputs require an isolated normally-open contact or switch (rated at 24 Vdc, 20 mA
minimum) connected between the alarm input and common terminal. All control wiring and switch
contacts are customer-supplied.
LAN and telephone drops for use with Minislot connectivity cards must be supplied by the customer.
The UPS battery detect signal wiring from a UPS building alarm must be connected to the battery
disconnect device.
Program the battery detect building alarm to read battery open and for normally open contacts.
A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided, but is not required
for normal operation.
Battery detect and 48 Vdc shunt trip wiring should be a minimum of 18 AWG.
The REPO feature opens all switchgear in the UPS cabinet and isolates power from your critical load. Local
electrical codes may also require tripping upstream protective devices to the UPS.
The REPO switch must be a latching-type switch not tied to any other circuits.
A jumper wire must be connected between pins 3 and 4 on the REPO terminal block if using a normally-
closed REPO switch.
REPO wiring should be a minimum of 18 AWG and a maximum of 16 AWG.
The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements.
The maximum distance between the REPO and the UPS cannot exceed 150m (500 ft).
Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac or 28
Vdc.
Alarm relay wiring should be a minimum of 18 AWG (recommended 18 AWG).
UPS Installation Plan and Unpacking