52 Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
if wiring external parallel pull chain connections, proceed to paragraph
4.11.6 Installing External Parallel Pull Chain Control Wiring and Connections; if wiring Minislot connections,
proceed to paragraph 4.11.7 Installing Minislot Interface Connections; if wiring REPO connections,
proceed to paragraph 4.12 Installing a REPO Switch; otherwise, proceed to Step 16.
16. Close the UPS outside door and secure the latch.
Figure 22. Interface Terminal Locations
Pull Chain and
CAN Terminals
Interface
Terminals
Minislot
Communication
Bays
Top of UPS
Figure 23. Interface Terminal Detail
Minislot Communication Bay 2
Minislot Communication Bay 1
Minislot Communication Bay 3
Minislot Communication Bay 4
Cabinet Stiffener Bar
RS-232
Host USB
Pull Chain and
CAN Terminals
Device USB
Relay Output Terminals
REPO Terminals
Building Alarm Terminals
UPS System Installation