EATON BiWire Flexi Installation Manual (PR215-216-520-03 15-03-16, PINSTFLEXIINST) March 2016 www.eaton.com 32
Technical Specifications
V 18.15-30.7V
Auxiliary Output Imax 50mA
Fuse 50mA PTC
UNMONITORED INTPUTS
Class Change Type Open Circuit = Normal Panel Operation
Short Circuit = Activate All Sounders
COMMUNICATION PORTS
Repeater Port (use of this port is outside
Type RS485
the scope of EN54 certification)
Nodes 1
ENVIRONMENTAL
Operating temperature -5 °C to +40°C
Relative Humidity 93% +/-3% non-condensing
IP Rating IP30
MECHANICAL
Dimensions 375mm Wide x 366mm Tall x 134mm Deep
Weight (excluding batteries) 2.25kg
Material PC ABS Front and Rear
CABLING
Cable Access 29 x 20mm drill positions - Slots for rear cable entry
Cable Type
Firetuf FT120 / FP200
Cable type 2 core 1.5mm, 2 screened fire rated cable,
500m (max per zone)
COMPLIANCE
Compliance to standards EN54 Part 2 CIE & Part 4 PSE, BS5839-pt1