Easy-Start ES Instruction Manual
Pre-Installation
INSTALLATION
2-13
Application Considerations
Model Number ES360 Starts-Per-Hour
Curr. Starting Start Percent Off-Time
Limit Current Time
AC Amps Sec. 0% 10% 20% 30%
2 120 200 300 400
250% 900
5 60 100 120 160
10 30 50 60 80
20 16 25 30 40
2 100 150 200 250
300% 1080
5 40 60 100 120
10 20 30 45 60
20 10 20 25 30
2 60 100 140 180
400% 1440
5 30 40 50 60
10 15 20 25 30
20 8 10 12 16
2 40 60 80 100
500% 1800
5 20 30 40 50
10 10 15 20 25
20 4 8 10 12
Starts-Per-Hour ES360
Table 2-7
Model Number ES500 Starts-Per-Hour
Curr. Starting Start Percent Off-Time
Limit Current Time
AC Amps Sec. 0% 10% 20% 30%
2 200 240 360 480
250% 1250
5 80 120 160 200
10 40 60 80 100
20 20 30 40 50
2 120 200 240 300
300% 1500
5 60 80 100 120
10 30 40 50 60
20 15 20 25 30
2 80 120 160 200
400% 2000
5 40 60 80 100
10 20 30 40 50
20 10 15 20 25
2 60 80 100 120
500% 2500
5 25 30 40 50
10 10 15 20 25
20 4 8 12 16
Starts-Per-Hour ES500
Table 2-8