Easy-Start ES Instruction Manual
Pre-Installation
INSTALLATION
2-14
Application Considerations
Model Number ES560 Starts-Per-Hour
Curr. Starting Start Percent Off-Time
Limit Current Time
AC Amps Sec. 0% 10% 20% 30%
2 100 180 300 400
250% 1400
5 50 80 100 120
10 24 40 60 80
20 12 20 30 40
2 80 140 200 240
300% 1680
5 40 60 80 100
10 16 20 30 40
20 8 16 20 24
2 50 100 120 140
400% 2240
5 20 30 40 60
10 8 16 20 24
20 4 8 12 16
2 30 40 60 100
500% 2800
5 12 20 30 40
10 4 8 12 16
20 - 2 4 6
Starts-Per-Hour ES560
Table 2-9
Model Number ES750 Starts-Per-Hour
Curr. Starting Start Percent Off-Time
Limit Current Time
AC Amps Sec. 0% 10% 20% 30%
2 180 240 320 400
250% 1875
5 80 100 120 150
10 40 50 70 80
20 20 25 30 40
2 120 200 240 300
300% 2250
5 60 80 100 120
10 30 40 50 60
20 10 20 25 30
2 80 120 150 180
400% 3000
5 30 40 50 60
10 15 25 30 35
20 8 10 12 16
2 60 80 100 120
500% 3750
5 25 30 40 50
10 10 15 20 25
20 4 8 10 12
Starts-Per-Hour ES750
Table 2-10