15INSTALLATION AND OPERATION MANUAL 25-16328-B November 2020 www.eaton.com
Section 1: System installation and design
Technical specification
Power specification
Mains Fuse : 1.6A Slow Blow
Nominal Voltage : 230 Vac + 10%, -15%
Nominal Current : 75mA
The Panel is protected by an internal thermal device, this requires no maintenance.
Batteries
Number of Batteries : 2
Manufacturer: : YSP12-7
Capacity : 7 Ah
Battery Fuse : 4A Quick Blow (F4)
Maximum battery current; : 3.5 Amps
Inputs
Addressable Loops
Max Number : 1 or 2 (Panel depending)
Max Loop Load per loop : 350 mA
Max Number of Addressable : 200
Devices per loop
Class Change : Operated by external volt free contact
Outputs
Conventional sounder circuits
Number of sounder circuits : 2
Total sounder Load : 1.5 Amp
Sounder Circuit Fuses (F1/2) : 1.6 Amp (Quick Blow)
End of line device : 210Ω + Diode
AUX 1
Max Load : 1 Amp
Fused (PTC2) : 1.1A polyswitch