EFX48 e-Fuse System Operation
Copyright © 2019 Eaton Corporation. All Rights Reserved.
IPN March 2019
109
Watchdog events
HTTP(S) failed account log on attempts and SNMP-V3 message
authentication/encryption failures
Configuration change events (the log does not record details of configuration change
just that a change has happened along with the associated User ID
Clock changes
All alarm events ( even if severity is ‘none’)
Note that Alarm Log entries for alarms that are not configured (ie severity is set to ‘none’)
appear in the log with ‘(unused) appended at the end of the log entry. This is so that conditions
that would otherwise have raised an alarm are entered into the log even if the alarm itself has
not been generated.
All log entries include:
Time and date stamp
Short event description and/or User ID
Data Log entries
There are 3 different types of Data log entries:
Load Log entries
String Log entries
Rectifier Log entries
The Load Log entries include:
All output load currents
Example log entry:
27-Jun-2018T09:35:50 Load currents 0.00, 12.05, 0.00, 15.23, 0.00, 0.00
Date
Time
Load output 1 to 6 current /A