Maintenance
Copyright © 2019 Eaton Corporation. All Rights Reserved.
IPN March 2019
131
Step 3 - Check cell/monobloc terminals
1 Check the terminal connections of the cell/monobloc are correctly tightened and
clean.
Refer to the battery manufacturer's instructions for correct terminal torque
settings.
2 Press the navigation switch on the front panel of the EFX48 to cancel the alarm.
3 If the alarm clears then the fault is fixed. No further action is required.
Step 4 - Service or replace faulty cell/monobloc (if required)
1 If the alarm is still present then follow the battery manufacturer’s instructions on
servicing or replacing the faulty cell/monobloc.
2 After the faulty cell/monobloc has been serviced or replaced clear the alarm (see
Step 3).
Procedure complete