NETWORK
SNMP
MMI
name
MMI
reference
MIB reference
Parameter
description
Factory
Default*
min max
Step
size
Host
addressing
networkHostName
Name DU-X
#serial
no
Character string up to 32
characters
Address type
networkHostAddressType
Address type Ipv4 Ipv4 / ipv6 / direct
IPv4 address
networkHostAddress
Host address 128bit address
IPv4 netmask
networkSubnetMask
Subnet mask 32bit address
IPv4 gateway
networkGatewayAddress
Gateway
address
128bit address
networkIpv6Prefix
Ipv6 prefix 128bit address
networkSnmpVersion
SNMP version V3 v1 / v2c / v3
networkSnmpWriteCommunit
y
SNMP write
community
“public”
Character string up to 32
characters
networkSnmpReadCommunity
SNMP read
community
“private
”
Character string up to 32
characters
networkSnmpAuthUsername
SNMP user
name
“snmpus
er”
Character string up to 20
characters
networkSnmpAuthPassword
SNMP auth
password
blank Character string up to 20
characters
networkSnmpPrivPassword
SNMP priv
password
blank 16 bytes
networkSnmpEnterpriseId
SNMP
enterprise ID
534 n/a n/a n/a
networkSnmpProductId
SNMP product
ID
0x1101 n/a n/a n/a
networkTrapVersion
SNMP trap ver V3 v1 / v2c / v3
networkTrapRepeatPeriod
SNMP trap
repeat period
(mins)
1 1 30 1
networkTftpAddressType
Tftp address
type
unknow
n
Unknown / ipv4 / ipv6
networkTftpAddress
Tftp address blank 32bit ipv4 or 128bit ipv6 address
networkTftpTrigger
Tftp trigger blank Character string up to 32
characters
* Factory defaults may not be correct for your installation. You need to set-up your own configuration file to