Parameters
04/10 MN04020001Z-EN
80
P3.9 419 / Fixed frequency, binary value B0 3
Allocation of the function to control signal terminals same as P3.2.
The binary connection of three digital inputs enable calling seven
fixed frequencies (eight fixed frequencies if parameter P6.2 = 0 is
set).
The limitation of the fixed frequencies is done based on
parameters P6.3 (minimum frequency) and P6.4 (maximum
frequency).
The switch between the individual fixed frequencies is done with
the acceleration time and deceleration times in P6.5 and P6.6.
Input (binary) Fixed frequency
B0 B1 B2 (Factory setting)
FF0, P10.1 = 5 Hz,
only if P6.2 = 0
X FF1, P10.2 = 10 Hz
X FF2, P10.3 = 15 Hz
X X FF3, P10.4 = 20 Hz
X FF4, P10.5 = 25 Hz
X X FF5, P10.6 = 30 Hz
X X FF6, P10.7 = 40 Hz
X X X FF7, P10.8 = 50 Hz
P3.10 420 / Fixed frequency, binary value B1. 4
Allocation of the function to control signal terminals same as P3.2.
P3.11 421 / Fixed frequency, binary value B2. 0
Allocation of the function to control signal terminals same as P3.2.
P3.12 1020 / Deactivate PID controller. 6
Allocation of the function to control signal terminals same as P3.2.
When switching on +24 V power, the PID controller is blocked via
the assigned control signal terminal (DI1 to DI6).
P3.13 1400 / Thermistor input (currently deactivated). 0
Assignment of control signal terminal as per P3.2.
P3.14 1401 / External brake, feedback signal (N/O) 0
Assignment of control signal terminal as per P3.2.
P3.15 1402 / Change acceleration/deceleration time. 0
Assignment of control signal terminal as per P3.2.
Switch acceleration time from acc1 (P6.5) to acc2 (P6.19).
Switch deceleration time from dec1 (P6.6) to dec2 (P6.20).
P3.16 1403 / Stop acceleration/deceleration time. 0
Assignment of control signal terminal as per P3.2.
Stops all acceleration (P6.5, P6.19, P14.9) and deceleration times
(P6.6, P6.20, P14.10).
PNU ID Access right
RUN
Value Description Factory setting
(P1.3)