38 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Table 14. Supplied External Wiring Terminal Hardware Kit (Continued)
Part
Size
Quantity Terminals Used On Eaton Part Number
Flat Washer
M10
15
Ground
180500036-100
Flat Washer
M12
184
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180500036-120
Conical Washer
M10
15
Ground
180500037-100
Conical Washer
M12
92
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180500037-120
Nut
M12
92
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180200001-07
NOTE Bypass terminations are not applicable to IOM configurations.
Table 15. Recommended Installation Parts and Tools (Not Supplied by Eaton)
Part Size
Quantity
Manufacturer Part Number Notes
Long Barrel 2-Hole Lug
2/0 AWG
As required
Thomas & Betts 54862BE
Copper wire only
3/0 AWG
Thomas & Betts 54864BE
4/0 AWG
Thomas & Betts 54866BE
250 MCM Thomas & Betts 54868BE
300 MCM Thomas & Betts 54870BE
350 MCM Thomas & Betts 54872BE
400 MCM Thomas & Betts 54874BE
500 MCM Thomas & Betts 54876BE
Manual Hydraulic Crimp Tool
14 Ton 1 Thomas & Betts TBM14M
Die Set
N/A
1 Thomas & Betts 15506
Table 16. Separate Rectifier Input UPM Power Cable Terminations for the Power Xpert 9395-275/225, 9395-275/275, and
9395-250/228
Terminal Function Terminal Function
Size of Pressure
Termination
Tightening Torque
Nm (lb ft)
Type Screw
AC Input to each UPM
Rectifier
E1 Phase A 2 - #6-250 kcmil
42.4 (375) 5/16” Hex
E2 Phase B 2 - #6-250 kcmil
42.4 (375) 5/16” Hex
E3 Phase C 2 - #6-250 kcmil
42.4 (375) 5/16” Hex
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See Table 17 for conduit
requirements.
Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the same conduit. Neutral and ground
must be run in the same conduit as the phase conductors.
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one ground
conductor sized in accordance with NEC Table 250.122.
Conduit sizes listed are for copper wiring only.
UPS Installation Plan and Unpacking