Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15 39
Table 17. Power Cable Conduit Requirements
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
Number of
Conduits
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4 2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 3
Power Xpert 9395-825/650
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5 3 4
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 3
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4 2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
2-1/2
3
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5 3 4
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4 2
3
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 4
Power Xpert 9395-825/750
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5 3 5
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4 2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 3
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5 3 4
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 5
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4 2
3
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 4
Power Xpert 9395-825/825
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5 3 5
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4 2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5 3 5
400 Vac
AC Input to UPS Rectifier
4 2
3
(Each UPM)
UPS Installation Plan and Unpacking