Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15 41
Table 18. Recommended Input Circuit Breaker Ratings (Continued)
UPS Model
Input Rating
Load Rating
400V 480V
Power Xpert 9395-825/450
Power Xpert 9395-825/500
Power Xpert 9395-825/550
See Note
80% Rated
2000A 1600A
100% Rated 1600A 1200A
NOTE Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, these breaker sizes are
specified for an 825 kVA UPS.
Table 19. Separate Rectifier Input Recommended Input Circuit Breaker Ratings
UPS Model
Input Rating
Load Rating
400V 480V
Power Xpert 9395-825/650
Power Xpert 9395-825/750
Power Xpert 9395-825/825
80% Rated 600A 500A
100% Rated 500A 400A
Power Xpert 9395-825/450
Power Xpert 9395-825/500
Power Xpert 9395-825/550
80% Rated
600A 500A
100% Rated 500A 400A
NOTE Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, these breaker sizes are
specified for an 825 kVA UPS.
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings
from Table 19 in accordance with NEC ANSI/NFPA 70.
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load shown in Table 5, Table 6, Table 7or Table 8. The recommended line-to-line load
unbalance is 50% or less.
Bypass and output overcurrent protection and bypass and output disconnect switches are to be provided by
the customer. Module Output Breakers (MOBs) are to be provided by the customer. Table 20 lists the
recommended rating for bypass, output, and MOB circuit breakers. Bypass breakers are not required for IOM
configurations.
UPS Installation Plan and Unpacking