SPECIFICATIONS
Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide S 164201730 Rev 4
www.eaton.com/powerquality
56
Table 14. Environmental and Safety
Low Voltage Models High Voltage Models
Operating Temperature 0°C to 40°C (32°F to 104°F)
Storage Temperature -25°C to 40°C (-13°F to 104°F)
Relative Humidity Storage: 10–95% noncondensing
Operating: 20–95% noncondensing
Audible Noise Less than 40 dBA Normal mode, typical load
Less than 45 dBA (50 dBA for 3000 VA) Battery mode
Surge Suppression ANSI C62.41 Category B, IEC 61000-4-5
Safety Conformance UL 1778, UL 497A;
CSA C22.2, No. 107.1;
NOM-019-SCFI
UL 1778, UL 497A (data line only);
CSA C22.2, No. 107.1;
EN 62040-1-1, IEC 60950-1, IEC 50091-1-1
Agency Markings cULus, cUL cTUVus, CE
EMC FCC Part 15 Class A EN 62040-2 C1, AS 62040-2 C1,
FCC Part 15 Class B
Table 15. Battery
UPS Configuration 1000/1250 VA: (4) 12V, 7.2 Ah internal batteries
1500/1750 VA: (4) 12V, 9 Ah internal batteries
2200/2500 VA: (6) 12V, 7.2 Ah internal batteries
3000 VA: (6) 12V, 9 Ah internal batteries
EBM Configuration PW5130N1750-EBM2U: 48 Vdc, (2 stings of 4) 12V, 9 Ah batteries
PW5130N3000-EBM2U and PW5130N3000-EBM3U: 72 Vdc, (2 strings of 6)
12V, 9 Ah batteries
Type Sealed, maintenance‐free, valve‐regulated, lead‐acid