SPECIFICATIONS
Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide S 164201730 Rev 4
www.eaton.com/powerquality
57
Table 16. Battery Runtimes (in minutes)
Load UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
PW5130L1000-XL2U (with PW5130N1750-EBM2U)
100 VA/70W 112 440 841 1196 1530
250 VA/175W 59 255 570 725 975
500 VA/350W 25 125 225 305 422
750 VA/525W 16 78 140 210 155
1000 VA/700W 10 56 100 150 192
1000 VA/1000W 7 36 66 97 128
PW5130L1500-XL2U (with PW5130N1750-EBM2U)
150 VA/105W 90 302 495 710 920
375 VA/262W 45 150 270 410 530
750 VA/525W 19 61 121 185 250
1125 VA/787W 10 45 70 110 150
1500 VA/1050W 7 32 58 84 111
1500 VA/1400W 4 22 40 55 77
PW5130L2200-XL2U (with PW5130N3000-EBM2U)
195 VA/136W 119 426 608 1082 1450
488 VA/341W 55 185 370 639 810
975 VA/682W 23 105 190 285 370
1463 VA/1045W 12 56 105 150 220
1950 VA/1365W 8 38 65 114 152
1950 VA/1920W 5 27 48 70 97
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.