SPECIFICATIONS
Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide S 164201730 Rev 4
www.eaton.com/powerquality
58
Table 16. Battery Runtimes (in minutes)
+4 EBMs+3 EBMs+2 EBMs+1 EBMUPS Internal BatteriesLoad
PW5130L3000-XL2U / PW5130L3000-XL3U / PW5130G3000-XL2U (with PW5130N3000-EBM2U or PW5130N3000-EBM3U
depending on UPS height)
300 VA/210W 80 270 500 705 901
750 VA/525W 39 143 308 370 482
1500 VA/1050W 16 62 117 160 210
2250 VA/1575W 8 35 59 85 105
3000 VA/2100W 5 24 40 59 82
3000 VA/2700W 3 17 32 47 62
PW5130i1250-XL2U (with PW5130N1750-EBM2U)
125 VA/115W 119 430 741 1052 1363
313 VA/288W 32 150 267 384 502
625 VA/575W 15 58 100 143 185
938 VA/863W 6 42 77 113 148
1250 VA/1150W 5 29 54 79 104
PW5130i1750-XL2U (with PW5130N1750-EBM2U)
175 VA/160W 80 245 410 575 740
438 VA/400W 24 96 168 240 312
875 VA/800W 9 36 62 89 115
1313 VA/1200W 6 24 42 60 79
1750 VA/1600W 3 16 28 41 53
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.