INPUT ISOLATION TRANSFORMER INSTALLATION
EATON Powerware
®
9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev F www.powerware.com
19
Input
Output
L1
L2 (208V)
L2 (240V)
L1
L2
N
GND
Edge Grommet
Pilot Holes in Conduit Landing
Figure 10. Input Isolation Transformer Hardwiring
NOTE Input neutral is supplied by the input isolation transformer.
Table 2. Input Isolation Transformer Terminal Block Wiring
Wire Function Terminal Position Input Circuit Breaker Rating Minimum Wire Size* Tightening Torque
Input
L1 TB1-1
8kVA 60A 3AWG(26.7mm
2
)
L2 (208V) TB1-2
10 kVA
80A
2AWG(33.6mm
2
)
2
25 lb in
L2 (240V) TB1-3
15 kVA
100A
.
1AWG(42.4mm
2
)
.
m
Output
L1 TB1-4
8kVA 4AWG(21.2mm
2
)
L2 TB1-5
10 kVA
3AWG(26.7mm
2
)
2
25 lb in
Neutral TB1-6
15 kVA
.
2AWG(33.6mm
2
)
.
m
Ground
Output TB1-7 8AWG
25 lb in
Input TB1-8 8AWG
(2.83 Nm)
*Useonly75°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger
AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.