SPECIFICATIONS
EATON Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide S 164201393 Rev C www.powerware.com
100
Table 15. Isolation
Models 0650C and 0660C Output
Neutral-to-Ground Bonding
±3% load regulation (under any line, load, or battery condition)
Neutral is carried through from input to output; a separate neutral-to-ground
bond is not required.
Model 0650I, 0660I, and 0660J
Isolation, Including Output
Neutral-to-Ground Bonding
True, separately derived power source as defined by National Electrical Code
Article 250-5d, with output neutral bonded to ground. No direct connection
between input and output; neutral-to-ground bond is required; other local codes
may take precedence.
Table 16. Split-Phase Model Specifications (ASY-0673)
3 kVA, 2500 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 16A 15A
220 15A 14A
208 14A 14.5A
2
5
A
2
8
5
W
(
0
9
8
k
B
T
U
h
)
220 13A 14A
25A 285W (0.98 kBTU
hr)
230 14.5A 13A
240 14A 12.5A
6 kVA, 5000 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 32A 30A
220 30A 28A
208 28A 29A
4
0
A
5
7
0
W
(
1
9
5
k
B
T
U
h
)
220 26A 28A
40A 570W (1.95 kBTU
hr)
230 29A 26A
240 28A 25A
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant
power module.