SPECIFICATIONS
EATON Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide S 164201393 Rev C www.powerware.com
101
Table 16. Split-Phase Model Specifications (ASY-0673) Continued
9 kVA, 7500 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 48A 45A
220 45A 42A
208 42A 43.5A
220 39A 42A
60A 860W (2.93 kBTU
hr)
230 43.5A 39A
240 42A 37.5A
12 kVA, 10000 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 64A 60A
220 60A 56A
208 56A 58A
220 52A 56A
80A 1145W (3.90 kBTU
hr)
230 58A 52A
240 56A 50A
15 kVA, 12500 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 80A 75A
220 75A 70A
208 70A 72.5A
220 65A 70A
100A 1430W (4.88 kBTU
hr)
230 72.5A 65A
240 70A 62.5A
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant
power module.