SPECIFICATIONS
EATON Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide S 164201393 Rev C www.powerware.com
102
Table 16. Split-Phase Model Specifications (ASY-0673) Continued
18 kVA, 15000 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 96A 90A
220 90A 84A
208 84A 77A
220 78A 84A
125A 1720W (5.85 kBTU
hr)
230 87A 78A
240 84A 75A
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant
power module.
Table 17. Universal Model Specifications (ASY-0674)
3 kVA, 2100 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 14A 15A
208 13.5A 14.5A
220 13A 14A
25A 285W (0.98 kBTU/hr)
230 12.5A 13A
240 12A 12.5A
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant
power module.