SPECIFICATIONS
EATON Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide S 164201393 Rev C www.powerware.com
103
Table 17. Universal Model Specifications (ASY-0674) Continued
6 kVA, 4200 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 28A 30A
208 27A 29A
220 26A 28A
40A 570W (1.95 kBTU/hr)
230 25A 26A
(
)
240 24A 25A
9 kVA, 6300 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 42A 45A
208 40.5A 43.5A
220 39A 42A
60A 860W (2.93 kBTU/hr)
230 37.5A 39A
(
)
240 36A 37.5A
12 kVA, 8400 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 56A 60A 80A 1145W (3.90 kBTU/hr)
208 54A 58A 80A 1145W (3.90 kBTU/hr)
220 52A 56A 80A 1145W (3.90 kBTU/hr)
230 50A 52A 80A 1145W (3.90 kBTU/hr)
240 48A 50A 80A 1145W (3.90 kBTU/hr)
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant
power module.