SPECIFICATIONS
EATON Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide S 164201393 Rev C www.powerware.com
104
Table 17. Universal Model Specifications (ASY-0674) Continued
15 kVA, 10500 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 70A 75A
208 67.5A 72.5A
220 65A 70A
100A 1430W (4.88 kBTU/hr)
230 62.5A 65A
(
)
240 60A 62.5A
18 kVA, 12600 Watts
Voltage Input Current* Output Current Input Service*
Heat Dissipation
Normal Mode
200 84A 90A
208 81A 87A
220 78A 84A
125A 1720W (5.85 kBTU/hr)
230 75A 78A
(
)
240 72A 75A
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant
power module.