Chapter 3: Technical data/ratings
8 SC9000 EP medium voltage drives IB020001EN—February 2016 www.eaton.com
Table 3. Dimensions
Notes
1
Contact factory.
2
Contact factory for 1150 hp.
Output
voltages
Motor Cabinet size (inches)
Redundant blower
additional heightFLA hp Width Height Depth
Frame A
2400 69–114 300–500 65 92 50 21.11
3300
1
48–112 300–700 65 92 50 21.11
4160 38–140 300–1150
2
65 92 50 21.11
Frame B
2400 134–223 600–1000 95 92 50 13.21
3300
1
128–240 800–1500 95 92 50 13.21
4160 155–248 1250–2000 95 92 50 13.21
Frame C
2400 279–390 1250–1750 131 92 50 12.25
3300
1
280–320 1750–2000 131 92 50 12.25
4160 279–372 2250–3000 137 92 50 12.25
Frame D
2400 448–561 2000–2500 172 92 50 18.8
3300
1
360–480 2250–3000 172 92 50 18.8
4160 403–558 3250–4500 222 92 50 18.8
Frame E
3300
1
520–640 3250–4000 222 92 50 20.22
4160 589–744 4750–6000 246 92 50 20.22