EasyManua.ls Logo

Eaton SC9000 EP - Chapter 4: Handling, Storage, and Installation; General Information

Eaton SC9000 EP
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4: Handling, storage, and installation
SC9000 EP medium voltage drives IB020001EN—February 2016 www.eaton.com 9
Chapter 4: Handling, storage,
and installation
General information
WARNING
Tall structure—may tip over if mishandled. May cause
bodily injury or equipment damage. Do not remove from
skid until ready to secure in place. Read handling
instructions below before moving.
Medium voltage drives are extremely heavy and the moving
equipment used in handling must be capable of supporting
the weight of the drive. Confirm this capability prior to
starting any handling operations with the drive. Refer to the
charts below for standard SC9000 EP shipping section
weights. These weights are approximate. Refer to the job
specific drawings for the weights of each shipping section.
The drive should be kept in an upright position. If the
equipment is received in the horizontal position, notify the
carrier of possible damage, and restore the drive to the
vertical position as soon as practicable.
Upon receipt, immediately inspect the drive for any signs of
visible or concealed damage that might have occurred during
shipment. If damage is found, it should be noted with the
carrier prior to accepting the shipment, if possible. Carefully
unpack the equipment sufficiently to check for concealed
damage. Verify that there are no bent, broken or loose
components. Review the drive nameplate to ensure that
the marked ratings match the order specifications.
Table 4. 2400 V AFD typical shipping section weights (lb)
Frame hp
Shipping sections
TotalTransformer Inverter Main disconnect Incoming
A 300 6125 6125
350 6225 6225
400 6325 6325
450 6525 6525
500 6725 6725
B 600 6085 1740 7825
700 6435 1740 7825
800 6785 1740 8525
900 7085 1840 8925
1000 7685 1840 9525
C 1250 8085 1840 900 10,825
1500 8685 2040 900 11,625
1750 9085 2140 900 12,125
D 2000 9335 2540 1850 1300 15,025
2250 10,435 2640 1850 1300 16,225
2500 11,535 2640 1850 1300 17,325

Table of Contents