System Options Menu
Page 55
Unconfirmed alarm: keypads and loudspeakers sound
immediately and run for the Siren Time.
Confirmed alarm: the control unit waits for any Siren Delay
(see page 46), and then starts the alarm sound at sirens and
restarts the sound at all keypads and loudspeakers. This
runs for the Siren Time.
Unconfirmed alarm: No alarm sounds.
Confirmed alarm: the control unit waits for any Siren Delay,
and then starts the alarm sound at all keypads loudspeakers
and sirens. This runs for the Siren Time.
Siren On
Unconfirm
The control unit operates the siren for all alarms (and overrides any Siren Delay).
Confirm
When the system is set, the control unit does not activate the siren(s) until a
confirmed alarm occurs.
The behaviour of sounders and sirens is described in Table 6.
Unconfirmed Reset
This is available only when Confirmation Mode is set to DD243 or BS8243. The setting for
this option overrides System Options – User Options – User Reset – Zone Alarms (see
page 49).
User
The user can reset after an unconfirmed alarm.
Installer
The user cannot reset after an unconfirmed alarm; the installer must do it.
Note:
If a user silences an alarm within the Abort Time (page 57), the alarm will not
require an installer reset.
These options apply to intruder alarms only and not to Hold-Up Alarms.
Confirmed Reset
This is available only when Confirmation Mode is set to DD243 or BS8243. The setting for
this option overrides System Options – User Options – User Reset – Zone Alarms (see
page 49).
User
The user can reset after a confirmed alarm.
Installer
The user cannot reset after a confirmed alarm; the installer must do it.
Note: If a user silences an alarm within the Abort Time (page 57), the alarm will not
require an installer reset.