XS series operating manual 
 
XS user manual v0.55  - 138 - 
Ground continuity measurement 
 
On  a  unit  or  an  electrical  device  using  or  generating  hazardous  voltages,  ground  continuity 
measurements insure that all the accessible protective parts are correctly connected to the protective 
earth connection wire. 
 
This measurement is almost a low resistance measurement except that it has to be performed with a 
high current, mostly in AC . 
 
The  principle  is  to  flow  a  current  between  each  metallic  accessible  parts  and  the  protective  earth 
connection, to measure the voltage drop between the 2 parts and to check with the Ohm’s law that the 
equivalent resistance is lower than the standard required value. 
 
Current selection 
 
The measurement current is defined by the safety standards which have to be used for each product. 
According to the main standards, this high current is comprised between 10 and 25 A AC or equal to 2 
times the nominal operating current of the device. 
The choice is justified by the fact that the protective earth connections have to be able to flow the fault 
current for the maximum value of the unit operating current and this during the reaction time of the other 
protective devices (fuses, breakers, etc...) 
 
Voltage selection  
 
This is the open voltage of the current generator used for the measurement. This voltage, mostly given 
by  each  safety  standards  is  mandatory  a  low  value  (lower  than  the  threshold  defining  a  hazardous 
voltage) but it must allow the measurement current flowing, taking care of the voltage drops between the 
generator and the measurement points. 
 
The open voltages are comprised between 6 and 12 AC volts. 
 
 
Test time  
 
Unlike  a  simple  resistance  measurement,  the  time  that  the  current  is  being  flowing  for  the  ground 
continuity measurement is important because of the ‘Safety’ function of the tested connection. 
Beyond  the  ohm  value  evaluation,  it  is  mandatory  to  test  the  quality  of  the  connection  to  the  earth 
potential (diameter of  the  wire,  solders quality, screwing  quality,  ...). A  manufacturing  fault  of  one of 
these connections may in certain circumstances give an immediate correct ohm value, but increasing 
quickly by heating causes by the high current value used for the test : this high current can produce a 
break of the wire (wounded wire, which diameter becomes too small). 
 
This is why some standards are requiring a minimum test time from 1 to 5 minutes for this measurement. 
Other standards don’t give any time indication, but it is advised to apply for type test a minimum time of 1 
minute and for series tests at least 10 seconds.