HCAT TE - HCAN TE
30 English 04/03
CnF Appliance configuration parameters Value
CP Compressor parameters Value
FAn Fan parameters Value
ALL Alarm parameters Value
LIST OF ACCESSIBLE - DISPLAYABLE PARAMETERS
Parameter Description Unit of measurement
Note: while the parameters are being set, the COMPRESSOR and ELECTRIC RESISTOR LEDs flash, alternating with
the DEFROSTING LED.
ALARM DISPLAY
I A
MALFUNCTION CAUSE REMEDY
Values display indication
E00
Remote switch set to OFF
(automatic reset)
Position the remote switch to ON
Reset the switch
Reset the jumper between terminals 6 and 7
Values display indication
E01
High pressure switch tripped.
manual reset after three trips in an hour
Check for fault (see high discharge pressure
page 31)
Reset manually
Values display indication
E02
High pressure switch tripped.
automatic reset for the first three trips in an hour
Check for fault
Values display indication
E04
Compressor and/or fan thermal overload switch
tripped (manual reset)
Verify compressor motor and/or fan motor
Reset manually
Values display indication
E07
BP3 pressure transducer fault
(automatic reset)
Check electrical connections
Replace component