D397-51-880 Issue E
Page 24 © Edwards Limited 2014. All rights reserved.
Edwards and the Edwards logo are trademarks of Edwards Limited.
MAINTENANCE
5 MAINTENANCE
5.1 Fault finding
In the event of a Profibus module failing to respond check the following:
Table 9 - Fault finding guide
Symptom Fault
Power LED not lit No DC supply or internal regulator faulty.
Off-line not lit and Error LED flashing. Address selection is above 125, correct the
address and re-power unit.
Off-line LED is lit and Error LED is lit. Unsuitable parameterisation or configuration,
check extended diagnostics for module number.
Off-line LED is lit and Error LED is not lit. Check unit’s address matches that being used
by the master. Check Profibus cable
connected. Check Profibus master is on-line.
Power LED is lit and all other LED’s are not lit. Serial connection to control unit disconnected
or faulty or control unit not powered on.
Data exchange LED is lit but data is not
changing.
Serial connection has become faulty after
entering data exchange. Check extended
diagnostics for serial comms lost indication.