Battery parameters
Function
Switch-on delay
The EFOY Pro fuel cell does not start immedi-
ately if the switch-on voltage only drops below
the set threshold level temporarily. The device
only starts automatically if the switch-on volt-
age is still below this threshold level after the
switch-on delay of 60 seconds. For example,
with the factory default of 12.3 V for lead-acid
batteries, the switch-on voltage must drop be-
low 12.3 V for at least 60 seconds in order for
the EFOY Pro fuel cell to start.
If loads with a high rate of power consumption
are operated temporarily, this value must be
set in accordance with the operating times of
these loads.
Switch-on voltage
The EFOY Pro fuel cell switches on at the set
voltage and charges the battery.
Setting too high a value for the switch-on volt-
age results in frequent starting of the EFOY Pro
fuel cell. Setting too low a value for the switch-
on voltage results in damage to the battery.
The default value for lead batteries is 12.3 V,
which corresponds to approx. 50% of the bat-
tery charge condition.
Switch-off voltage
If the battery voltage reaches the set level, the
EFOY Pro fuel cell switches off, provided that
the value set for the "Switch-off current" pa-
rameter has also been reached.
Please note your battery's end-of-charging
voltage. Note the charging recommendations
provided by the battery manufacturer.
Switch-off current
The EFOY Pro fuel cell switches off if the cur-
rent drops below the set switch-off current.
If you want the battery voltage to serve as the
only switch-off parameter, set the maximum
value, as the current is always below this value
in EFOY Pro fuel cells.