Operation
Page 49
Permitted value ranges for Lead-acid, -gel & AGM batteries (12 V)
Factory
defaults
Min.
Max.
User-defined
value:
Switch-on voltage
12,3 V
11,0 V
13,0 V
Switch-off voltage
14,2 V
13,5 V
14,7 V
Switch-off voltage
(Hybrid)
14,7 V
13,5 V
15,5 V
Switch-off current
EFOY Pro 800
EFOY Pro 2400
2,0 A
4,0 A
1,0 A
4,0 A
10,0 A
10,0 A
Switch-on delay
60 s
2 s
300 s
Absorption time
180 min
0 min
300 min
Max. charge time
24 h
2 h
120 h
Altitude up to
1500 m
0 m
2000 m
Permitted value ranges for Lead-acid, -gel & AGM batteries (24 V)
Factory
defaults
Min.
Max.
User-defined
value:
Switch-on voltage
24.6 V
22.0 V
26.0 V
Switch-off voltage
28.4 V
27.0 V
29.4 V
Switch-off voltage
(Hybrid)
29,4 V
27,0 V
31,0 V
Switch-off current
EFOY Pro 800
EFOY Pro 2400
1.0 A
2.0 A
1.0 A
2.0 A
5.0 A
5.0 A
Switch-on delay
60 s
2 s
300 s
Absorption time
180 min
0 min
300 min
Max. charge time
24 h
2 h
120 h
Altitude up to
1500 m
0 m
2000 m