EasyManua.ls Logo

EG4 LiFePower4 - 2 Technical Specifications

EG4 LiFePower4
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
2. TECHNICAL SPECIFICATIONS
MODULE OPERATING PARAMETERS
PARAMETER
BMS
RECOMMENDED
VO LTAGE
51.2V -
CAPACITY
100Ah -
CHARGING VOLTAGE (BULK/ABSORB)
56.8V -
SOC CUTOFF
44.8V 20%*
CHARGING CURRENT
100A (Max. continuous) 30A
DISCHARGING CURRENT
100A (Max. continuous) -
MAXIMUM CONTINUOUS DISCHARGE RATE
5.12kW
NAMEPLATE ENERGY CAPACITY
5.12kWh
BMS PARAMETERS
CHARGE
SPEC
DELAY
RECOVERY
CELL VOLTAGE PROTECTION
3.8V 1s 3.45V
MODULE VOLTAGE PROTECTION
60.0V 1s 55.2V
OVER CHARGING CURRENT 1
>102A 20s -
OVER CHARGING CURRENT 2
≥120A 3s -
TEMPERATURE PROTECTION
<23°F or >158°F
<-5°C or >70°C
1s
<32°F or >140°F
>0°C or 60°C
DISCHARGE
CELL VOLTAGE PROTECTION
2.3V 1s 3.1V
MODULE VOLTAGE PROTECTION
44.8V 1s 48.0V
OVER CHARGING CURRENT 1
>102A 30s 60s
OVER CHARGING CURRENT 2
>150A 3s 60s
SHORT-CIRCUIT
>300A <0.1ms -
TEMPERATURE PROTECTION
<-4°F or >167°F
<-20°C or >75°C
1s
>14°F or <149°F
>-10°C or <65°C
PCB TEMP PROTECTION
>221°F (>105°C) 1s <176°F (<80°C)

Related product manuals