SHORT INTERRUPTIONS
Short interruption is a v oltage dr op of l ess t han 9 7.0% f rom n ominal ( event
deactivate o n 7 7.6%). M in d uration 1 0 m s, M ax d uration 3 m in. ev ents are
counted in the entire observation window of 1 week. Total events (N) allowed
is: 2.
LONG INTERRUPTIONS
Long interruptions are the same as short ones but with a longer duration (longer
than short interruption maximum time). Long interruptions events are counted
within observation window of 1 week. Total events (N) allowed is: 1.
TEMPORARY OVERVOLTAGE (SWELLS)
www.GlobalTestSupply.com