1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 112/192
ACF6
The number of compressor of the 2 circuits (CF04 + CF05) is:
> 4
> 4 with no direct compressor start-up (CO10 0) or the number of steps
is > 0 (CF06),
> 2 and the intermittent valve is configurated
Pump-down function but at least in one circuit:
The pump-down solenoid relay is not present
No pump-down pressure switch or evaporating probe when
the pump-down is enabled with unit in start
Or
No low pressure switch configurated.
The compressor configuration with CF04 and CF05 but not the relay
outputs:
Main relay of the compressor
Intermittent valve when enabled with the ON / OFF time (CO08 / CO09
> 0)
When the by-pass time >0 and there is no partialization or by-pass
valve configured
Coil 2 of part-winding start up
Requested step valve for screw compressor are configurated
One relay is configured as:
Compressor not selected in CF04 or CF05
Intermittent valve configured but CO08 =0 and CO09 =0
By-pass gas valve configured but by-pass time = 0
Coil 2 of part winding start up configured but direct start up selected
Wrong configuration of the capacity step valve
ACF7
Evaporator pump configuration:
Enabled (CO16 >0) but the relay of the water pump is not configured
Not enabled (CO16=0) but the relay of the water pump is configured
Condenser pump configuration:
Enabled (CO21 >0) but the relay of the water pump is not configured
Not enabled (CO21=0) but the relay of the water pump is configured
Water pump enabled for antifizee prevention:
if Ar24=1 and Ar25=0 (water pump enabled for antifreeze prevention
but is not configured the probe)
ifAr25=1 and not probe configurated to control the water pump for
antifreeze
if Ar34=1 and Ar35=0 (water pump enabled for antifreeze prevention
but is not configured the probe)
ifAr35=1 and not probe configurated to control the water pump for
antifreeze
ACF8
Cooling / heating regulation probe configuration
The regulation probe selected by ST09 or ST10 parameters is not
properly configured
The compressor rack regulation probe selected by Cr01 is not present
on the configured probes