EasyManua.ls Logo

Emerson Dixell iChill IC207D - Page 113

Emerson Dixell iChill IC207D
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 113/192
Label on alarm
visualization menu
ACF9
Recovery function enabled but whitout resources needed (heat recovery probe
or digital input, heat recovery valve, condenser probe)
AC10
Compressor inverter controlled
2 anologue output configured to control the same compressor
One analog output is configured to control a compressor via inverter but
none relays is configured as compressor
If the unit is configured as condensing unit and a compressor is
configured as compressor inverter controlled
AC11
Compressor with different power capacity enabled and:
One analog output is configured as output for compressor inverter
controlled
one of the compressor has capacity power = 0
the regulation is not a neutral zone
the compressor is configured with capacity step
AC12
Free cooling function enabled and:
None relay is configured as free cooling
FS41 and FS42 select a probe not configured in CF parameters
If FS21 < FS22
If FS01=2 and CF97=2
If it is not respected the following condition:
FS38 < St07 <= FS37
AC13
Domestic hot water function enabled and:
None relay is configured as valve 1
None probe is configured as probe 1 of domestic hot water
Valves mounted on water circuit and valves configured to be switched
off in STD-BY or OFF
Domestic hot water priority defined by digital input and none digital input
configured for this function
FS49=1 and the regulation is in neutral zone
AC15
Hybrid exchangers enabled and:
dF27-dF29> dF28-dF30 or
dF27>dF28 or
dF32+dF34> dF31+dF33 or
dF32>dF31
Origin
Wrong programming
Reset
Correctly programming
Restart
Automatic
Symbol
On the display the symbol is blinking
Action
Alarm relay + buzzer ON
ACFL: condenser flow alarm (differential Pressure switch)
Label on alarm
visualization menu
ACFL condenser flow alarm

Table of Contents