1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 114/192
Digital input active for the time set in AL55 after the water pump is on and, after
the digital input itself is activated, for the time set in AL57.
Alarm not enable if AL14=0
Alarm enabled in chiller only if AL14=1
Alarm enabled in heat pump only if AL14=2
Alarm enabled in chiller and heat pump if AL14=3
Digital input not active for the time AL58.
Automatic – Manual after AL56 (Reset procedure in Menu function).
On the display the symbol is blinking
Alarm Relay + and buzzer on only during normal running conditions.
ACP1 - ACP1 Condenser pump mintenance
Label on alarm
visualization menu
ACP1 (Condenser 1 pump maintenance)
ACP1 (Condenser 2 pump maintenance)
Pump running hours > Hour counter setpoint
Hour reset in function menu
On the display the symbol is blinking
Only display warning messages
AEE Eeprom alarm
Label on alarm
visualization menu
On the display the symbol is blinking
AEFL: evaporator flow alarm (differential pressure switch)
Label on alarm
visualization menu
AEFL evaporator flow alarm
Digital input active for the time set in AL15 after the water pump is on and, after
the digital input itself is activated, for the time set in AL17.
Digital input not active for the time AL18.
Automatic – Manual if the digital input is active for AL16 seconds (Reset
procedure in Menu function).
On the display the symbol is blinking
Alarm Relay + and buzzer on only during normal running conditions.
ATTENTION
The alarm relay and the buzzer are activated only if the alarm appears during normal running conditions.
When the temperature setpoint has been reached and CO16/CO21= 2, the icon blinks without alarm.
NOTE ABOUT THE FLOW ALARM
CO16 / CO21=0 Water pump not enabled.
The alarm is managed only if one digital input is configured as flow switch, the restart is always automatic.
CO16 / CO21=1 Water pump with continuous control.