EasyManua.ls Logo

Emerson Dixell iChill IC207D - ACFL: condenser flow alarm (differential Pressure switch)

Emerson Dixell iChill IC207D
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 114/192
Origin
Digital input active for the time set in AL55 after the water pump is on and, after
the digital input itself is activated, for the time set in AL57.
Alarm not enable if AL14=0
Alarm enabled in chiller only if AL14=1
Alarm enabled in heat pump only if AL14=2
Alarm enabled in chiller and heat pump if AL14=3
Reset
Digital input not active for the time AL58.
Restart
Automatic Manual after AL56 (Reset procedure in Menu function).
Symbol
On the display the symbol is blinking
Action
Alarm Relay + and buzzer on only during normal running conditions.
Loads
OFF
ACP1 - ACP1 Condenser pump mintenance
Label on alarm
visualization menu
ACP1 (Condenser 1 pump maintenance)
ACP1 (Condenser 2 pump maintenance)
Origin
Pump running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Symbol
On the display the symbol is blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
AEE Eeprom alarm
Label on alarm
visualization menu
AEE
Origin
Wrong eeprom data
Reset
-------
Restart
Manual
Symbol
On the display the symbol is blinking
Action
Alarm relay + buzzer ON
Loads
OFF
AEFL: evaporator flow alarm (differential pressure switch)
Label on alarm
visualization menu
AEFL evaporator flow alarm
Origin
Digital input active for the time set in AL15 after the water pump is on and, after
the digital input itself is activated, for the time set in AL17.
Reset
Digital input not active for the time AL18.
Restart
Automatic Manual if the digital input is active for AL16 seconds (Reset
procedure in Menu function).
Symbol
On the display the symbol is blinking
Action
Alarm Relay + and buzzer on only during normal running conditions.
ATTENTION
The alarm relay and the buzzer are activated only if the alarm appears during normal running conditions.
When the temperature setpoint has been reached and CO16/CO21= 2, the icon blinks without alarm.
NOTE ABOUT THE FLOW ALARM
CO16 / CO21=0 Water pump not enabled.
The alarm is managed only if one digital input is configured as flow switch, the restart is always automatic.
CO16 / CO21=1 Water pump with continuous control.

Table of Contents

Related product manuals