1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 119/192
Label on alarm
visualization menu
ArtC (clock alarm)
Origin
Wrong setting
Reset
After clock adjustement
Restart
Manual in function menu
Symbol
On the display the symbol is blinking
Action
Alarm relay + buzzer ON
Regulation
Loads
Not changed
Energy saving
Disabled if controlled by RTC
Unit ON/OFF
Disabled if controlled by RTC
ArtF Clock failure
Label on alarm
visualization menu
ArtF (clock failure)
Origin
Clock failure
Reset
Replace the instrument
Restart
Manual in function menu
Symbol
On the display the symbol is blinking
Action
Alarm relay + buzzer ON
Regulation
Loads
Not changed
Energy saving
Disabled if controlled by RTC
Unit ON/OFF
Disabled if controlled by RTC
ASAn Domestic hot water pump mintenance
Label on alarm
visualization menu
ASAn (Domestic hot water pump maintenance)
Origin
Pump running hours > Hour counter setpoint
Reset
Hour reset in function menu
Restart
Manual
Symbol
On the display the symbol is blinking
Action
Alarm relay + buzzer ON
Regulation
Action
Only display warning messages
Loads
Not changed
ASLA Failed Communication With I/O Expansion
Label on alarm
visualization menu
ASLA
Origin
Failed communication with I/O expansion
Reset
Automatic when the communication is working
Restart
Automatic
Symbol
blinking
Action
Alarm relay + buzzer ON
Regolatori
Loads
OFF